Steel Structure Counter Flow Open Water Cooling Tower

Application:Casting, forging, air compressor, central air conditioner, ground source heat pump, printing machine

MNTNK Application

" MSTNK" type apply to the low cooling temperature ( Temp . < 45℃ or not higher than the location wet bulb temperature too much ) or needs a small cooling range projects ( △T=5-10℃ )


MSTHK Application

Apply to the projects which have large cooling temp drop ( △T = 15-50℃ ) , or high temp inlet ( ≥45C℃) . If the work place has requirement to keep low noisy and enviromental protection , we also could provide Low noise type cooling tower .

Details

2

MSTNK Process principle


Without cooling coils, the heated working fluid be sprayed to the PVC fills, and reacts with cold inlet air for heat transferring, then the heat is exhausted out of the tower by the fan, and the working fluid is collected back to the water tank for circulating.


MSTHK Process principle


Simiary with MSTNK, but MSTHK model has two sides into wind, and the fan canister design to maximize. So that there has  largest air flow space. Wide-chord hollow fan blade, reduce the nosie.


Characteristics


1. Steel structure is more stabilization

The tower out shell, water tank, support, exhaust air canister and other spare parts all are steel material. So the cooling towers have mechanical strength, good stability.

2. Cheaper

Relative to closed cooling tower, there is no cooling coils inside, simple structure. So the price will be more cheaper.

3. High-performance

Relative to FRP cooling tower, steel tower has stable structer, smooth operation, higher precision design standard, more secure performance indicators.

4. Easy installation & maintainance

Modular overall shipments, the lager models only need to connect the upper box and bottom box, it will reduce the installation difficulty and outerdoor operation cost. 

There is maintenance tunnel inside and large space, convinent to clean pvc fills and replace parts.

5. Environmental protection

There is no enviroment pollution risk of steel material. After  reached the end of the service life, the steel material also could be recycle without secondary pollution.


Technical Parameters of Cross Flow Open type

Model

Flow Rate(m³/h)

Fan

Pipe Size(DN)

Net weight(kg)

Operating weight(kg)

Dimension(mm)

Power

Diameter
(mm)

Inlet

Outlet

Sewage

Supply

Machine Size L*W*H

Foundation sizeL*W

MSTHK-100

100

4

1500

100*2

125

25

25

1090

3900

1980*3200*3700

2080*3300

MSTHK-125

125

4

1800

125*2

150

32

25

1350

5050

2320*3600*3700

2420*3700

MSTHK-150

150

5.5

2000

125*2

150

32

25

1450

5900

2600*3800*3700

2700*3900

MSTHK-175

175

5.5

2000

125*2

150

32

25

1500

6560

2930*3800*3700

3030*3900

MSTHK-200

200

7.5

2400

150*2

200

32

25

1690

7660

3040*4300*3700

3140*4400

MSTHK-225

225

7.5

2400

150*2

200

32

25

1900

8750

2950*5080*4100

3050*5180

MSTHK-250

250

7.5

2400

150*2

250

40

40

1950

9250

3000*5300*4100

3100*5400

MSTHK-300

300

11

2800

150*2

250

40

40

2350

10600

3250*5550*4100

3350*5650

MSTHK-350

350

11

2800

150*2

250

40

40

2420

11700

3500*5800*4100

3600*5900

MSTHK-400

400

15

3000

150*4

300

40

50

2730

13150

3750*6050*4250

3850*6150

MSTHK-450

450

15

3000

150*4

300

50

50

2850

14500

4000*6300*4250

4100*6400

MSTHK-500

500

18.5

3000

150*4

300

50

50

3250

14750

4000*6300*4850

4100*6400

Notes:* Dates in the form is only for your reference, actual parameters should meet customers’ demands.

       * Design conditions: maximum flow rate ≤450m³/h, operating environment temp.≤31.5℃, wet bulb temp.≤28℃,humidity not higher than 85%,elevation below 1000m. (Taking antifreeze measures below 0℃)

       * Any queries for above parameters please contact our account executive.

 

 

Technical Parameters of Counter Flow Open type

 

Model

Flow Rate(m³/h)

Fan

Pipe Size(DN)

Net weight(kg)

Operating weight(kg)

Dimension(mm)

Power
(kw)

Diameter
(mm)

Inlet

Outlet

Sewage

Supply

Machine SizeL*W*H

Foundation size
L*W

MSTNK-100

100

4

1800

125

125

25

25

1180

3300

2250*2250*4070

2350*2350

MSTNK-125

125

5.5

2000

150

150

32

25

1340

4015

2500*2500*4070

2600*2600

MSTNK-150

150

5.5

2000

150

150

32

25

1640

4870

2750*2750*4570

2850*2850

MSTNK-175

175

7.5

2400

150

150

32

25

1830

5720

3000*3000*4570

3100*3100

MSTNK-200

200

7.5

2400

200

200

32

25

2020

6630

3250*3250*4570

3350*3350

MSTNK-225

225

7.5

2400

200

200

32

25

2060

6800

3300*3300*4570

3400*3400

MSTNK-250

250

7.5

2400

200

200

40

40

2290

7650

3500*3500*4770

3600*3600

MSTNK-300

300

11

2800

250

250

40

40

2570

8750

3750*3750*4950

3850*3850

MSTNK-350

350

11

3000

250

250

40

40

2800

9860

4000*4000*4950

4100*4100

MSTNK-400

400

15

3300

300

300

40

50

3350

12350

4500*4500*5150

4600*4600

MSTNK-450

450

15

3300

300

300

50

50

3640

13900

4800*4800*5150

4900*4900

MSTNK-500

500

15

3600

300

300

50

50

4070

15000

5000*5000*5600

5100*5100

Notes:* Dates in the form is only for your reference, actual parameters should meet customers’ demands.

       * Design conditions: maximum flow rate ≤450m³/h, operating environment temp.≤31.5℃, wet bulb temp.≤28℃,humidity not higher than 85%,elevation below 1000m. (Taking antifreeze measures below 0℃)

       * Any queries for above parameters please contact our account executive.

 


Feel free to request a quote by filling the following form and our professional sales engineer will reply within 24 hours.